24. Siemens PLC 24-3
S7-300MPI (HMI ADP, PC ADP, Helmholz SSW7 ADP)
Set [MPI SETTING] in the [Comm. Parameter] dialog of the V-SFT editor.
Highest MPI Address: Set the maximum value of the port numbers for the PLC or the V7 series.
Source No.: Set the V7-series port number.
Set different numbers for [Source No.] and [Local No.], and be sure that
[Source No.] [Highest MPI Address].
[Highest MPI Address] setting example
If port numbers “13” and “20” are selected respectively for the PLC and the V7 series, select
“31.”
TI500/505, TI500/505 V4
Item Setting on PLC
V7 Comm. Parameter Setting
HMI ADP
PC ADP
Helmholz SSW7 ADP
Baud rate 38400 bps 38400 bps (fixed) 38400 bps
Parity Odd (fixed)
Transmission
code
Data length 8 (fixed)
Stop bit 1 (fixed)
Local No. (PLC port number) 2 2
Item MPI SETTING
Highest MPI Address 15/31/63/126
Source No. (V7 port number) 0
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Parity None (fixed)
Transmission
code
Data length 8 (fixed)
Stop bit 1 (fixed)